Surge protection devices (SPDs) protect electrical equipment from voltage transients caused by lightning strikes, switching operations, and power system disturbances.

Surge Current Rating Selection

Select SPD rating based on location and exposure:

  • Service entrance (high exposure): 200kA-300kA per phase
  • Service entrance (standard): 100kA-150kA per phase
  • Distribution panels: 50kA-100kA per phase
  • Equipment protection: 20kA-50kA per phase

Protection Modes

Complete protection requires all modes:

  • L-L: Line-to-line protection
  • L-N: Line-to-neutral protection
  • L-G: Line-to-ground protection
  • N-G: Neutral-to-ground protection

Coordination Strategy

Implement coordinated protection:

  • Higher capacity SPD at service entrance
  • Lower capacity SPDs at distribution panels
  • 10-20 foot separation between levels
  • Cascade protection reduces stress on downstream devices